Aerial-Mounted Snow Switch
FEATURES
Automatic Activation - The system will only activate when needed which will save energy and operation costs.
The sensor turns on when moisture is present and the temperature reaches to the temperature you set.

Easy Installation - The snow sensor is mounted by either attaching the mounting hub to a rigid ½-inch or ¾-inch conduit
or by installing screws through the four mounting tabs provided. Wiring is performed by terminating your existing wiring to the pre-installed pigtails. The unit is housed in a two-gang PVC enclosure. The overall dimensions of the DS-2B are 4¾"x7"x2¾", and the unit weighs 2 pounds. The user may access all electronics by removing the four front cover screws.
|
 |

Adjustable Temperature Trigger Point - Trigger temperature (TT) is the set temperature in which
the device activates the systems and is adjustable from 34°F-44°F
using the “Temp Adjust” control. When ambient air temperature is below this
trigger point, precipitation is assumed to be snow or freezing rain. When above,
precipitation is assumed to be rain.

Smart System Ready - Buy the optional CS-1 cable and the snow sensor
can connect into compatible smart systems that will allow you to turn
your system on and off via telephone at a remote location.

|
Upgradeable Remote Activation - Control and monitor your BlueHeat snow melting system inside your home by
adding a remote control panel. The panels are mounted on a 1.75"x19" standard rack mount panel and have a range of
up to 1200' away. They provide basic DEICE ON status for the deicing system, along with MANUAL ON, AUTOMATIC, and STANDBY control capabilities.
|
 |

Adjustable Delay Off Cycle - "Delay Off" refers to the drying cycle timer of the snow sensor. The timer
allows the snow sensor to dry the heated surface through evaporation once
precipitation has stopped. The drying cycle reduces the chance of
moisture left behind refreezing into ice. This timer is restarted by
each precipitation detection. Therefore, the snow sensor will continue to
operate as long as precipitation is detected, then for the Delay Off period once the precipitation has stopped. All "sensor" modes provide a minimum 2-minute closure to reduce cycling of an external controller or feed
blower. When in "controller" mode, the Delay Off time can be adjusted from 30-90 minutes using the
"Delay Adjust" control.

Full 30A @ 240VAC Control - The snow sensor can be powered from either a 100-120 VAC
or 200-240 VAC 50/60Hz source. Peak power consumption is 15 watts. Voltage selection is performed by installing
provided jumpers onto the printed circuit board. The unit provides a single 240VAC @ 30A normally open load contact set.
This contact set is paralleled with a low power contact set to provide remote activation monitoring. Operational
temperature range is -40vC to +85vC.

Selectable Low Temperature Cutoff - The Low Temperature Cutoff (LTC) option will cause the sensor not to trigger if precipitation is detected below a certain temperature. However, if the deicing system has been activated, precipitation continues, and the ambient temperature drops below the set temperature, LTC will be ignored. This assures that water left behind on the surface during the heating cycle will not immediately refreeze into ice as a result of deactivating the deicing system.

Replaceable Precipitation Sensor - It is recommended that the DS-2B be powered down and the grid wiped clean with clear water at least once every 4 months. Heavy deposits may be removed using Scotch-Brite.
|
|